LAING AUTOCIRC PUMP

Operating Cost Savings Summary

Based on 3 bedroom home with 4 occupants, water heater 60 feet from farthest fixture, non-insulated ¾" copper hot water supply line with Laing Autocirc Undersink System Pump at the farthest fixture from water heater. 

Gas Water Heater

Chart Calculation Factors For Gas Water Heater:

1.  Savings of 34.2 gal./day of previously heated water wasted from discharging down drain.  (350 days/yr. = 11,970 gal./yr.)
2.  Water heater is set at an average temperature of 140°F, has an efficiency rating of 65%, and a heat rise temperature value of 100°F.
3.  The incoming water temperature is 40°F.
4.  Gas cost per therm includes taxes and charges.
5.  Gas savings in therms result from not having to heat wasted water less the gas used to offset piping heat losses. (101.71 therms/yr.)
6.  Additional piping heat losses are based on 10 BTU/hr./ft. in 60 feet of 3/4" uninsulated hot water supply piping.
7.  Water cost is based on $2.02/100 cu. ft. and sewer surcharge cost is based on $1.35/100 ft.3.  (Total water cost savings = $53.79/yr.)
8.  Cost to run pump = $1.24/yr. (Based on $0.10/kWh, pump running 4 min./hr., 16 hrs./day, and 350 days/yr.)
9.  Numbers are rounded off.

 

Electric Water Heater

Chart Calculation Factors For Electric Water Heater:

1.  Savings of 34.2 gal./day of previously heated water wasted from discharging down drain.  (350 days/yr. = 11,970 gal./yr.)
2.  Water heater is set at an average temperature of 140°F, has an efficiency rating of 100%, and a heat rise temperature value of 100°F.
3.  The incoming water temperature is 40°F.
4.  Electrical energy savings in kWh result from not having to heat wasted water less the energy used to offset piping heat losses. (1,924.69 kWh)
5.  Cost per kWh includes taxes and charges.
6.  Additional piping heat losses are based on 10 BTU/hr./ft. in 60 feet of 3/4" uninsulated hot water supply piping.
7.  Water cost is based on $2.02/100 cu. ft. and sewer surcharge cost is based on $1.35/100 ft.3.  (Total water cost savings = $53.79/yr.)
8.  Cost to run pump = $1.24/yr. (Based on $0.10/kWh, pump running 4 min./hr., 16 hrs./day, and 350 days/yr.)
9.  Numbers are rounded off.

Notes:

1.  Use of insulated copper supply line on Autocirc system would result in additional savings.
2.  Actual savings may differ from household to household depending on a variety of factors including water use habits, length of hot water supply line, number of home occupants, etc.

Above summary based on study and analysis prepared by Edward Saltzberg and Associates, consulting mechanical engineers. Copies of this detailed analysis are available on request from Laing Thermotech, Inc.

 